EPS Panel Fire Test Report
Our EPS sandwich panels have been independently fire-tested by SGS — one of the world’s leading testing and certification bodies — to AS/NZS 1530.3, the Australian standard for ignitability, flame propagation, heat release and smoke release.
SGS Accredited LaboratoryAS/NZS 1530.3:1999 Part 3Report No. AJFTS26007427R01
Test Results at a Glance
AS/NZS 1530.3 measures four early fire hazard indices — the lower the number, the better the result.
0 / 20
Ignitability Index
The lowest possible score. Specimens did not ignite under test conditions.
0 / 10
Spread of Flame Index
The lowest possible score. No flame propagation was recorded.
0 / 10
Heat Evolved Index
The lowest possible score. No measurable heat release contribution.
4 / 10
Smoke Developed Index
A low smoke result, comfortably within the 0–10 regulatory scale.
✓ 6 specimens tested — none ignited. No flashing was encountered; the only observation was a surface colour change.
What This Means For Your Project
Cool Rooms & Food Businesses
Butcher shops, cafes and food storage builds can reference an independent Australian-standard fire test when dealing with landlords, insurers and certifiers.
Sheds, Garages & Studios
Using EPS panels for lining or partitioning? These results give you documented evidence of low early fire hazard indices for council or building-approval conversations.
Buy With Confidence
Not all EPS panels on the market are tested. Ours are — by SGS, to the relevant Australian standard, with the report available for you to download and keep on file.
Report Details
| Test report number | AJFTS26007427R01_EN |
|---|---|
| Issued by | SGS-CSTC Standards Technical Services Co., Ltd (SGS Group) |
| Test standard | AS/NZS 1530.3:1999 — Methods for fire tests on building materials, components and structures, Part 3: Simultaneous determination of ignitability, flame propagation, heat release and smoke release |
| Sample tested | EPS sandwich panel, white, 50 mm thick, 16 kg/m³ core density |
| Client | Cool Room Master Pty Ltd, 75 South Terrace, Wingfield SA 5013 |
| Testing period | 2 – 10 September 2026 |
| Report date | 14 September 2026 |
Get a Copy of the Report
The summary document reproduces pages 1 and 3 of the original SGS report. The full report is available on request.
SGS AS/NZS 1530.3 Fire Test Report — Summary
Report No. AJFTS26007427R01_EN · Issued 14 Sep 2026 · 1.4 MB
Questions About Fire Compliance?
Fire and building requirements vary by state, council and application. Talk to us about your project — or visit our Wingfield showroom to see and compare the panels in person.
Test results relate to the specimen tested (50 mm white EPS sandwich panel, 16 kg/m³ core density) under AS/NZS 1530.3:1999 laboratory conditions and do not by themselves constitute a claim of compliance for any specific building application. Always confirm requirements with your certifier or local authority.